Refrigerated
Containers
|
||
|
Body. The refrigerated container will provide an insulated and temperature controlled load compartment for the carriage of deep-frozen or refrigerated food. Rear doors to the container will give access to the load compartment. The container is to be colored white. |
||
|
Container Construction.
Container Construction.
The container body sides, roof and front bulkhead are to be paneled
with a thermally insulated sandwich material faced with suitably robust
materials. All paneling is to comply with current EU Carriage of Food
Regulations. The paneling is to be securely fastened to the body framing
and all joints are to be capped and sealed with a non-toxic flexible compound.
Load Compartment
Access. Access to the load compartment is to be by vertically split
double rear doors with a minimum door height of 1.90m and minimum opining
width of 2.20m. The rear door opening is to be centered in the rear face
of the vehicle. The doors are to be insulated to the same standard as
the body and fitted with seals designed to minimize loss of cooled air.
All doors must be lockable and able to be securely fastened when in the
open position.
Container Lighting.
One vapor proof florescent light to be fitted to the interior of the
roof along its longitudinal centerline. They are to be operated by a robust,
door switch that shall be activated automatically when the door is open. Cooling and Insulation
System. The load compartment cooling system is to be capable of operation
by a 3-phase electrical power system which must meet the applicable provisions
of IEE Wiring Regulations 16th Edition. Stowage is to be provided for
up to 10m of cable with EU standard waterproof mains power connectors.
Temperature controllers and thermometers are to be provided on the outside
of the container adjacent to the power system controls showing the selected
and the actual internal temperature of the container roof. The cooling
and insulation system must be capable of maintaining the following internal
temperatures with an external ambient shade temperature of 43o C. When
static and fully loaded after a period of 3 hours with no operation of
the cooling system: minus 18o C. Condensing Unit.
Shall be second hand reconditioned 3 phases and semi hermetic complete
with sight glass, filter dryer, high/low pressure control and solonoid
valve. And shall be charged with ozone friendly refrigerant. Control Powel.
Shall have M.C.B. protecting each circuit, shall fitted with phase failure
device. Defrost timer and change over switch to switch over from -18o
C freezer to +4o C refrigerated. |